Insulation board classification, inspection standards and precautions for use

Insulation board is also called insulation rubber pad, insulation pad, insulation gasket, insulation blanket. Insulation panels are now widely used in substations, power plants, power distribution rooms, laboratories, and live live operations in the field. The physical and mechanical properties are good, and it has excellent insulation properties. Next, the editor will introduce the classification, inspection standards and precautions for insulation boards.


绝缘板_看图王.jpg


   Insulation board classification


(1) According to the voltage level, it can be divided into 5kv, 10kv, 20kv, 25kv and 35kv.

(2) According to the color, it can be divided into: black rubber pad, red rubber pad, green rubber pad.

(3) According to the thickness, it can be divided into: 0.15mm-130mm length and width specifications: 1020 * 1220, 1220 * 1220, 1000 * 2000, 1244 * 2440, 1500 * 3000.

  General use configuration

(1) 5KV insulating rubber pad. Thickness: 3mm. Specific gravity: 5.8KG / m2. Color: red, green, black.

(2) 10KV insulating rubber pad. Thickness: 5mm. Specific gravity: 9.2KG / m2. Color: red, green, black.

(3) 15KV insulating rubber pad. Thickness: 5mm. Specific gravity: 9.2KG / m2. Color: red, green, black.

(4) 20KV insulating rubber pad. Thickness: 6mm. Specific gravity: 11KG / m2. Color: red, green, black.

(5) 25KV insulating rubber pad. Thickness: 8mm. Specific gravity: 14.8KG / m2. Color: red, green, black.

(6) 30KV-35KV insulating rubber pad. Thickness: 10mm12mm. Specific gravity: 18.4KG / m2; 22KG / m2. Color: red, green, black.


   Insulation board inspection standard (take 8mm insulating rubber sheet as an example)


1. Appearance:

â‘  The depth and height of the spots do not exceed the thickness tolerance of the rubber sheet;

② Within every square meter of bubbles, there are no more than 5 bubbles with an area of ​​less than 1cm, and the distance between any two bubbles is not less than 40mm;

â‘¢ The depth and length of impurities do not exceed 1/6 of the thickness of the rubber sheet;

â‘£The uneven edge or sea-like width does not exceed 10mm, and the length does not exceed 1/10 of the total length of the rubber sheet;

⑤ No cracks.

2. Hardness (Shore A): 55-70.

3. Tensile strength and elongation at break: 1) Tensile strength (Mpa) ≥5.02) Elongation at break ≥250%.

4. Fixed extension (150%) permanent deformation ≤ 25%.

5. Hot air aging (70 ℃ * 72h): The tensile strength reduction rate is ≤30%.

6. Water absorption≤1.5%.

7. Electrical insulation performance test: 1) Voltage withstand test: 25KV (effective value), keep for 1min, there should be no breakdown phenomenon; 2) Breakdown voltage test ≥35KV (effective value).


   Precautions for using insulation board


  1. Has good arc resistance and anti-leakage traceability

Because the insulation board works outdoors, it is directly affected by atmospheric conditions, and it is also contaminated by oil smoke, water vapor and coal powder on the mixed traction railway line. The surface is prone to dust particles, which leads to insulation leakage. The arc further carbonizes the surface of the insulation board, and the carbon traces are distributed in irregular dendrites on the surface of the insulation board to damage the insulation. Therefore, it is required that the insulation board must be strict in process requirements to ensure the smoothness of the surface, make it difficult to adhere to dirt, and have good arc resistance. Before using the insulation board, the samples should be tested for tracking resistance and arc resistance, and can only be used after reaching the national IA2.5 level and arc resistance standards.

   2. Do not make it work in the state of surface discharge, improve the electrical service life

The insulating plate is used as the insulating medium between the contact net and the ground. Due to the small space under the bridge, the contact wire may come into contact with the insulating plate and produce surface discharge. Epoxy glass fiber reinforced plastic and SMC molding compound have a good linear relationship, but unsaturated poly glass fiber reinforced plastic has a broken line relationship, but all indicate that the insulating material is under a strong electric field (especially under surface discharge conditions), and its service life will be greatly shortened Therefore, in the project, try not to make the insulating plate work under the surface discharge state. The contact net suspension structure should try to use isolated suspension as far as possible, so that there is an air gap between the contact wire and the insulating plate to form secondary insulation. At this time, most of the voltage of the contact net to the ground is added to the air gap, and the voltage on the insulating plate is low. Only when the electric locomotive passes under the bridge, the contact wire may make short-term contact with the insulating plate, so the isolation suspension is used. It can effectively prevent surface discharge and extend the electrical life of the insulating board.

The above is the entire content of the classification, inspection standards and precautions for the insulation board introduced to you by the editor. The insulating board is made of glue-type insulating material, and there should be no harmful irregularities on the upper and lower surfaces. It has excellent insulation performance, so that it can work in the environment with high dielectric constant in dry -35 ~ + 100 ℃ air.  